Cable type detectors are also known as Lineer Heat Detectors. Special cables are used to detect fire and transmit fire information to the central fire alarm detection system. LH’s are preferred where point type detectors can not be used. LHD’s have different types suitable for indoor or outdoor. LHD’s have three types according to the technology used.
Digital LHD cables work like fixed heat detectors. They have different models according to the alarm temperature and ambient temperature. Any additional controller is not required; LHD cables can directly be connected to the Fire Alarm System via input modules. Distance locator devices can be used optionally. These devices directly shows alarm point which can be useful at long distances. Digital LHD cables have different types according to the usage area. If it will be used at corrosive environment or outdoor; stainless steel option should be preferred. Basically digital LHD cable melts at alarm point and creates alarm; then sends this information to the main fire alarm detection system. Digital LHD cables must be replaced after fire situation. Digital LHD cables are most cost effective types of LHD’s.
Analog LHD cables work like fixed and/or rate of rise heat detectors. They must be used with a controller. Alarm temperature can be set on controller. Analog LHD cables have special conductor inside which detects alarm at set point. Controller receives temperature information from cable and evaluates if it is a fire alarm or not. Controller transmit fire alarm information to the main fire alarm system via input modules. Analog LHD cables are reusable after fire if not harmed.
Fiber Optical LHD cables work like fixed and/or rate of rise heat detectors. They must be used with a controller. Alarm temperature can be set on controller. Controller receives temperature information from cable and evaluates if it is a fire alarm or not. Controller transmit fire alarm information to the main fire alarm system via input modules. Fiber Optical LHD cables are reusable after fire if not harmed. Fiber Optical LHD cables are much more sensitive and faster than other LHD technologies. Fiber Optical LHD cables can be used with long distances like 8-10km.
The choice is made based on budget, distance, and reusability needs. Digital cable is economical but single-use, since it melts during activation. Analog cable offers adjustable temperature thresholds and detects heat without melting. Fiber optic cable, meanwhile, provides pinpoint location detection over very long distances of 8 to 10 km.
No, the entire cable does not need to be replaced. The damaged section that melted and short-circuited during the fire is cut out of the line. Splicing in a new section of digital cable using dedicated waterproof junction boxes is enough to bring the system back into operation.
Protection is achieved by selecting the outer jacket to match the risks of the environment. Steel-armored models are used where there is a risk of mechanical impact or rodents. UV-resistant nylon jackets are preferred for outdoor areas, while high-resistance fluoropolymer coatings are chosen for areas with chemical or solvent exposure.
A single controller can instantly measure temperature changes at every meter along 8 to 10 km of cable and report the exact location of a fire. It is immune to electromagnetic fields, does not corrode, and reliably triggers emergency scenarios such as jet fans without error.
Integration is achieved through addressable input / contact monitoring modules. Digital cables are connected to the module via a resistor, while the dry-contact alarm/fault relay outputs on the controllers of analog and fiber optic systems are wired into these modules and relayed to the main panel.
You can call by phone or write via the contact form,
Our experts will respond to you in detail as soon as possible.